Warehouse Fire Safety: Flue Space, Sprinklers and Flue Guard™/Flue Keeper™

Flue space is the open channel built into every pallet rack layout so heat can rise and sprinkler water can reach a fire. Here is what it is, why blocked flue space is a real fire-code problem, and how Flue Guard™ and Flue Keeper™ keep it open without slowing down day-to-day operations.

Warehouse aisle between two back-to-back pallet rack rows showing open flue space with sprinkler piping on the ceiling directly above

Longitudinal & transverse

The two kinds of flue space

NFPA 13

The sprinkler code that drives flue space rules

One-person install

Flue Guard™ installation

US Patent #7,857,152

Flue Keeper™ (Original)

Plan your layout before you buy

Configure upright height, beam width, bay count, and load levels in our free 3D Pallet Rack Configurator, then get an instant bill of materials and request a quote.

What flue space is

Flue space is not wasted space in a warehouse layout — it is a designed-in gap that lets heat and water move through a rack the way a fire sprinkler system expects them to. There are two kinds, and both show up on nearly every pallet rack systems layout:

Flue space Where it runs What creates it
Longitudinal The aisle-like gap running the length of the racking, typically between the backs of two back-to-back rows Row spacing between back-to-back frames
Transverse The gap between adjacent pallets sitting side by side on the same beam level Loading pattern — how far apart pallets are placed on the beam

Picture a warehouse aisle from above: pallet rack row, aisle, pallet rack row, then another gap, then the next pair of rows. That gap between back-to-back rows is longitudinal flue space. Now look at a single beam level from the front: two or three pallets sit side by side with a small gap between them. That gap is transverse flue space. Both are supposed to stay open, top to bottom, through every level of the rack.

Why flue space matters for sprinklers

Fire sprinkler design for palletized storage — the design approach behind NFPA 13, the widely adopted standard for sprinkler system installation — leans on open vertical and horizontal channels running through the rack. Two things happen in those channels during a fire:

  • Heat rises through them fast enough to trigger sprinkler heads at or near the fire, instead of a head somewhere else in the building reacting late.
  • Water comes down through them to reach the burning product directly, instead of being caught and shed by the tops of sealed cartons on the level above.

When flue spaces are blocked — by pallets pushed too far back, boxes hanging over an edge, or product stacked wider than the beam — both of those mechanisms are degraded. That is why flue space is treated as a life-safety and property-protection issue, not a housekeeping preference.

In-rack sprinkler head and pipe mounted between pallet rack beam levels with clear open flue space beside it

Our own warehouse storage compliance guide covers the broader NFPA storage-height, aisle and sprinkler-coordination picture; this page focuses specifically on the flue space inside the rack itself.

How flue space gets lost in day-to-day operations

Flue space is almost always correct on the day a rack is installed. It gets lost gradually, as normal warehouse activity pushes pallets around:

  • Pallet push-through. A forklift driver seats a pallet a little too far, and it protrudes into the aisle behind the rack, closing the longitudinal gap.
  • Oversized or overhanging loads. A pallet wider than the beam, or product that bulges past the pallet edge, narrows or closes the transverse gap to the next pallet.
  • Tight, fast putaway. Under pressure to fill every slot, product gets set closer together than the layout intended.
  • Mixed pallet sizes. A layout designed around one pallet footprint loses its flue space when a different-sized load is stored in the same bay.
  • No physical stop. Without something in the rack that limits how far a pallet can go, there is nothing to correct human error consistently, shift after shift.

Who checks this

Local fire marshals have the authority to enforce flue-space and sprinkler-clearance requirements during inspections, and a warehouse found out of compliance can be ordered to correct its storage or racking before it can keep operating that way. Physical hardware that maintains the gap is more reliable over time than instructions alone.

Galvanized steel pallet rack row spacer bolted between two back-to-back upright frames to hold a fixed flue space gap

Flue Guard™: keeping longitudinal flue space open

Flue Guard™ is a rack-mounted stop, a registered trademark of Rack Safety Products, LLC, built to keep the longitudinal flue space between back-to-back rows open on a permanent basis, without relying on operators to judge distance by eye every time they set a pallet.

Universal fit. It works with roll-formed or structural racking from any manufacturer, and fits beams of any length or depth — no custom-length beams and no swapping existing rack to add it.

One-person install. It attaches with high-strength tek screws, so it goes on new rack or gets retrofitted onto rack that is already loaded and in service, without a two-person crew or special tools.

A defined, repeatable gap. It is built to hold a consistent minimum flue space (6 inches on the version most commonly installed), so the same standard applies at every bay, on every shift, regardless of who is driving the forklift.

Flue Guard™ vs. a pallet rack backstop beam

The traditional alternative is a backstop beam or wire-mesh backstop spanning the back of the rack. Here is how the two approaches compare on the points that matter most in an operating warehouse:

Flue Guard™ Backstop beam
Installation One person, tek screws, fast Two installers, longer install time
Compatibility Universal — any brand, any beam length Often needs a matched beam length or wire mesh sized to the bay, sometimes forcing wider row spacing
Cost & freight Lower cost per unit and lighter to ship Higher unit cost and freight due to weight and size
Effect on flue space Maintains an exact, unobstructed minimum flue space Can itself encroach on the flue space it is meant to protect, risking non-compliance

Flue Keeper™: protecting transverse flue space

Where Flue Guard™ targets the longitudinal gap between back-to-back rows, the Original Flue Keeper™ (US Patent #7,857,152) targets the transverse gap between pallets sitting side by side on the same beam level. It is a physical stop that keeps boxes and product from encroaching sideways into that gap, which is exactly where in-rack and ceiling sprinklers rely on a clear path down through the storage.

  • The standard Flue Keeper™ is 42 inches by 3 inches and installs on new or existing racking in either direction.
  • It is designed to meet fire code expectations for transverse spacing across the US, but the exact clearance your building needs still depends on your sprinkler design, commodity class and local fire code — confirm specifics with your sprinkler contractor or fire marshal before finalizing a layout.
  • Like Flue Guard™, it is a physical control: once installed, it keeps doing its job without depending on an operator judging the gap correctly every time.

Auditing your racking for flue space

A quick walk-through with these questions catches most flue-space problems before an inspector does:

  • Stand at the end of a back-to-back row and sight down the longitudinal gap. Is it a straight, open channel end to end, or does it narrow or close anywhere?
  • Check pallets on the same beam level for gaps between them. Are any touching, or overhanging their pallet onto the neighboring one?
  • Look for oversized loads that were placed without adjusting for their width.
  • Ask whether any bay has a mixed pallet footprint that the original layout was not designed around.
  • If flue space keeps closing in the same bays, that is a sign the layout needs a physical stop — not a reminder to staff.

Our team can review a layout for flue-space, aisle and rack-spacing questions alongside a broader pallet rack design consultation, and our rack inspection and repair team can flag flue-space issues during a routine rack safety inspection. For long, exposed loads where a cantilever rack layout is in use, flue-space planning works a little differently — ask us about your specific layout.

Wide view of a high-bay warehouse with long rows of pallet racking and sprinkler piping running above every aisle

Flue space requirements by rack type and storage height

Once you know why flue space matters, the next question in any layout review is how much is required. For sprinklered rack storage, the International Fire Code answers it in Section 3208.3: flue spaces must follow Table 3208.3, and required flue spaces must be maintained. The table sets transverse and longitudinal widths by rack configuration, storage height and sprinkler arrangement. NFPA 13, the standard the sprinkler system itself is designed to, has its own flue provisions, also split at 25 ft of storage height. The values below come from the 2021 IFC.

Rack type Flue Ceiling sprinklers, storage up to 25 ft Ceiling sprinklers, storage over 25 ft In-rack sprinklers at every tier (any height)
Single-row Transverse 3 in 3 in, vertically aligned Not required
Single-row Longitudinal Not required Not required Not required
Double-row, Option 1 Transverse 6 in (note a) 3 in, vertically aligned Not required
Double-row, Option 1 Longitudinal Not required 6 in Not required
Double-row, Option 2 Transverse 3 in 6 in, vertically aligned Not required
Double-row, Option 2 Longitudinal 6 in Not required Not required
Multiple-row Transverse 6 in 6 in, vertically aligned Not required
Multiple-row Longitudinal Not required Not required Not required

“Ceiling sprinklers” means sprinklers at the ceiling with or without minimum in-rack sprinklers. Note a: where ESFR sprinklers protect the storage, the table allows 3-in transverse flues instead, provided at least every 10 ft. Random variations in flue width and alignment are allowed as long as the arrangement does not block water penetration. Source: International Fire Code 2021, Section 3208.3 and Table 3208.3 (same values in the Utah and Colorado adoptions).

Plan-view diagram of a double-row pallet rack between two aisles, with the longitudinal flue running between the backs of the rows and a transverse flue between side-by-side loads
Plan view: where the longitudinal and transverse flues sit in a double-row rack. Diagram: MH-USA
Front-view diagram of one pallet rack bay with three beam levels, showing the transverse flue between two loads kept open and lined up from floor to top
Front view: a transverse flue kept open through every beam level. Diagram: MH-USA

How to read the table

  • Double-row racks get two options. Up to 25 ft, Option 1 uses 6-in transverse flues with no longitudinal flue, and Option 2 uses 3-in transverse flues plus a 6-in longitudinal flue. Over 25 ft the pairing flips: Option 1 is 3-in transverse plus 6-in longitudinal, and Option 2 is 6-in transverse with no longitudinal flue. The right choice depends on beam length, load width and row spacing, so settle it before frames and row spacers are ordered.
  • Over 25 ft, transverse flues must line up. Every transverse flue in that column has to be vertically aligned from level to level.
  • Single-row and multiple-row racks never need a longitudinal flue in this table; their protection rests on transverse flues.
  • In-rack sprinklers at every tier remove the table requirement, but the sprinkler design may still assume open flues, so confirm with your sprinkler designer before closing gaps.
  • Protection devices. Section 3208.3.1 lets the fire code official require approved devices that protect required flues above the first tier, and those devices may not be removed or modified. This is the job hardware such as Flue Guard™ and Flue Keeper™ does.
  • Permit drawings. Section 3201.3 lists the dimension and location of transverse and longitudinal flue spaces among the items a high-piled storage permit submittal must show.

Measure the flue between loads, not between frames

Code flue widths are clear openings between stored loads. Pallets usually overhang the rear beam, so the gap between back-to-back frames on an empty rack is not the flue. Worked example: with a 3-in rear overhang on each side, a 6-in clear longitudinal flue needs the frames set about 12 in apart (3 + 6 + 3). Deeper pallets, extra overhang or loads pushed back too far all shrink that number, which is why row-spacer length should come from real load depth.

BHD Storage gives the same field advice: measure frame to frame, subtract the actual overhang on both sides, and check several beam levels.

Photo: BHD Storage Solutions

Long runs of back-to-back pallet rack with paired green upright frames, orange beams and wire decking, a narrow gap between each pair of frames
Low view across a wire deck on an orange pallet rack beam, with boxed loads on the levels above and open gaps between loads in each bay

Plan each bay so transverse flues survive putaway

Transverse flues come from loading math. Two 40-in-wide loads in a bay with about 96 in between uprights leave 16 in to share: hold 6 in in the center and roughly 5 in remains at each upright. Wider loads or three-wide bays tighten that quickly, so run the numbers for your actual pallet faces before choosing beam lengths.

Open pallet rack wire decking lets water pass down through each level, but it does not replace a required flue. Racks with solid shelves larger than 20 sq ft are a separate case that IFC Section 3208.2.2 sends to NFPA 13 protection.

Photo: BHD Storage Solutions

Editions, amendments and insurers

These are model-code values from one edition. Your state or city may enforce an older or newer IFC edition or local amendments, NFPA 13 sets its own flue rules for the sprinkler design, and some insurers apply stricter criteria. Treat the table as a planning starting point and confirm the governing numbers with your fire code official and sprinkler designer before you finalize a layout.

Shop Flue-Space & Rack Safety Products Online

Buy select items directly from our online store, or request a quote for volume, custom sizes and freight-rated orders.

Frequently asked questions

What is the difference between longitudinal and transverse flue space?
Longitudinal flue space runs the length of the aisle between the backs of two back-to-back rows of racking. Transverse flue space is the gap between pallets placed side by side on the same beam level. Both need to stay open for a rack-storage sprinkler design to work as intended.
Why does NFPA 13 care about flue space?
NFPA 13 is the widely adopted standard for installing fire sprinkler systems, and its approach to protecting palletized storage depends on open vertical and horizontal channels through the rack so heat can rise to trigger sprinklers and water can reach the fire. Blocking those channels reduces how effectively the sprinkler system can respond.
Can Flue Guard™ and Flue Keeper™ be installed on existing racking?
Yes. Both are designed for retrofit installation on racking that is already in service, as well as on new rack during the initial build-out, and neither requires taking a bay fully out of service for long.
Will Flue Guard™ and Flue Keeper™ work with the racking brand I already have?
Both are built to be universally compatible with roll-formed and structural racking across brands. Flue Guard™ fits beams of any length or depth without needing custom-sized replacement beams.
What should I do if a fire marshal flags flue space during an inspection?
Fix the physical cause, not just the day of the inspection: identify which bays are losing longitudinal or transverse space, add a permanent stop such as Flue Guard™ or Flue Keeper™ where pallets keep encroaching, and reconfirm the exact clearance your sprinkler design and local code require, since numeric requirements can vary by commodity class and rack depth.
Does keeping flue space open affect how much I can store?
It changes how a bay is loaded, not the rack’s structural capacity. Products for maintaining flue space are sized to hold the minimum required gap without wasting extra room, so the goal is consistent, code-appropriate spacing rather than a large capacity giveback.
Do you serve businesses outside Utah with these products?
Yes. Material Handling USA designs and supplies pallet rack systems and flue-space hardware for warehouses across Utah and the broader Intermountain region, and can help evaluate flue-space questions for existing racking or a new layout wherever your facility is.
How much flue space is required between back-to-back pallet racks?
Under the 2021 International Fire Code (Table 3208.3), a sprinklered double-row rack needs a 6-inch longitudinal flue between the backs of the rows in two cases: storage over 25 ft using Option 1, or storage up to 25 ft using Option 2, which pairs it with 3-inch transverse flues. The other options use wider transverse flues instead. Measure the 6 inches clear between loads, not between frames, and confirm the edition your jurisdiction enforces with your fire code official.
Do I need flue spaces if my racks have in-rack sprinklers?
The 2021 IFC flue table does not require transverse or longitudinal flues when in-rack sprinklers are installed at every tier. Racks protected by ceiling sprinklers, with or without minimum in-rack sprinklers, still need the flues in the table. Your sprinkler design and insurer can set their own criteria, so check the design documents before closing any gaps.

Ensure NFPA 13 flue-space compliance today

Don’t wait for a fire marshal inspection to find a blocked flue space. Talk with a specialist about Flue Guard™, Flue Keeper™ and your overall pallet rack layout. Free design consultation.

Headquartered in Salt Lake City, UT • Serving customers nationwide
Local service areas: Salt Lake City • Provo • Ogden • Park City • St. George • Logan • Lehi • Orem